Part Number 2519119-2

Circuit Breaker

Pricing & Availability

Submit this form for current pricing and availability of this NSN.
Part / NSN:
Qty:
Your Email:
Phone:
Ref. / PO #:
Company:
Your Name:

We do not share or sell your information to anyone.
Privacy | Terms

All major credit cards accepted as well as gov. p-cards
Part Number
DEMIL
Shelf Life
UOM
NIIN
Part:
2519119-2
Demil:
No
Shelf Life:
UOM:
NIIN:
001632093
NSN
National Stock Number:
5925-00-163-2093 5925001632093
TXT
Description:
Circuit Breaker
INC
INC
Item Name Code:
00136
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Single pole type
MRC:
A measurement of the longest dimension of the body,in distinction from width.ADAQ
Body Length:
3.000 inches
MRC:
A measurement taken at right angles to the length of the body,in distinction from thickness.ADAT
Body Width:
0.739 inches
MRC:
A measurement from the bottom to the top of the body,in distinction from depth.ADAU
Body Height:
2.402 inches
MRC:
The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.ADTV
Case Material:
Plastic
MRC:
None.AJEC
Boss Height:
0.188 inches
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
1
MRC:
Indicates the type and number of facilities by which the item is mounted.AXHR
Mounting Facility Type And Quantity:
2 terminal
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
20.0 amperes ac single location
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
120.0 ac single location
MRC:
Indicates the type and value of the maximum short circuit current that the item will successfully interrupt,per pole,at the specified rated voltage,expressed in amperes.CPRG
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
10000.0 ac single location
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent single location
MRC:
The means by which the trip mechanism is released.CPRJ
Trip Release Method:
Thermal-magnetic single location
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Time delay single location
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
25.0 single location
MRC:
The means provided to reposition the mechanism so that the device is ready to function.CPRQ
Reset Method:
Manual
MRC:
Indicates the type of mechanism provided for tripping main contacts.CPRR
Main Contact Tripping Mechanism Type:
Trip free
MRC:
Indicates the type and number of actuators provided for manual control.CPRT
Manual Actuator Type And Quantity:
1 toggle
MRC:
Denotes the action imparted by actuator operation.CPRW
Actuator Function:
Trip-reset
MRC:
An indication of the designated position of the actuator.CPRX
Actuator Position Designation:
At pole one
MRC:
The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.CQWN
Trip Delay Time In Seconds Per Rated Continuous Current:
120.000 at 200 pct single location
MRC:
Indicates the type of protection for which the inclosure is designed.CQXF
Inclosure Protection Type For Which Designed:
Fungus resistant
MRC:
The temperature of the medium surrounding the trip release at which it can be operated continuously.CRCF
Trip Release Ambient Tempurature Rating:
40.0 degrees celsius single location
MRC:
The cycles per second /hertz/ of the alternating current.FREQ
Frequency In Hertz:
60.0 single location
MRC:
Indicates the type and number of terminals for providing electrical connection.TTQY
Terminal Type And Quantity:
1 clip and 1 compression

Similar Circuit Breakers

« Circuit Breakers Catalog
Compare Now »
Clear | Hide