Part Number
DEMIL
Shelf Life
UOM
NIIN
Part:
3363mg4-25-120-2
Demil:
No
Shelf Life:
UOM:
NIIN:
005029276
NSN
National Stock Number:
5925-00-502-9276 5925005029276
TXT
Description:
Circuit Breaker
INC
INC
Item Name Code:
00136
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Multipole-single actuator type
MRC:
A measurement of the longest dimension of the body,in distinction from width.ADAQ
Body Length:
5.250 inches
MRC:
A measurement taken at right angles to the length of the body,in distinction from thickness.ADAT
Body Width:
3.000 inches
MRC:
A measurement from the bottom to the top of the body,in distinction from depth.ADAU
Body Height:
2.688 inches
MRC:
The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.ADTV
Case Material:
Plastic
MRC:
The center to center distance between terminals parallel to the length of the item.AEBP
Center To Center Distance Between Terminals Parallel To Length:
4.359 inches
MRC:
The center to center distance between terminals parallel to the width of the item.AEBQ
Center To Center Distance Between Terminals Parallel To Width:
1.000 inches
MRC:
The length of a straight line which passes through the center of an unthreaded mounting hole,and terminates at the circumference.AEBV
Unthreaded Mounting Hole Diameter:
0.190 inches
MRC:
The distance between centerlines of mounting facilities parallel to the length of the item.AEBY
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length:
4.359 inches
MRC:
The distance between centerlines of mounting facilities parallel to the width of the item.AEHA
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width:
0.984 inches
MRC:
None.AJEC
Boss Height:
0.219 inches
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
3
MRC:
Indicates the type and number of facilities by which the item is mounted.AXHR
Mounting Facility Type And Quantity:
4 unthreaded hole
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
25.0 amperes ac all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
120.0 ac all locations
MRC:
Indicates the type and value of the maximum short circuit current that the item will successfully interrupt,per pole,at the specified rated voltage,expressed in amperes.CPRG
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
5000.0 ac all locations
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent all locations
MRC:
The means by which the trip mechanism is released.CPRJ
Trip Release Method:
Magnetic all locations
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Instantaneous all locations and time delay all locations
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
MRC:
The ultimate time per pole in which the device must trip,expressed in seconds.CPRP
Ultimate Trip Time Per Pole In Seconds:
80.000 all locations
MRC:
The means provided to reposition the mechanism so that the device is ready to function.CPRQ
Reset Method:
Manual
MRC:
Indicates the type of mechanism provided for tripping main contacts.CPRR
Main Contact Tripping Mechanism Type:
Trip free
MRC:
The basic internal electrical configuration of the trip mechanism.CPSM
Internal Trip Release Configuration:
Series trip all locations
MRC:
The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.CQWN
Trip Delay Time In Seconds Per Rated Continuous Current:
20.000 at 200 pct all locations
MRC:
The cycles per second /hertz/ of the alternating current.FREQ
Frequency In Hertz:
60.0 all locations
MRC:
Indicates the type and number of terminals for providing electrical connection.TTQY
Terminal Type And Quantity:
6 screw

Similar Circuit Breakers