Part Number JGA36225

Circuit Breaker

Pricing & Availability

Submit this form for current pricing and availability of this NSN.
Part / NSN:
Qty:
Your Email:
Phone:
Ref. / PO #:
Company:
Your Name:

We do not share or sell your information to anyone.
Privacy | Terms

All major credit cards accepted as well as gov. p-cards
Part Number
DEMIL
Shelf Life
UOM
NIIN
Part:
jga36225
Demil:
No
Shelf Life:
UOM:
NIIN:
015875767

Part Information
J-frame; interrupting rating: 65ka at 240 vac, 35ka at 480 vac, 18ka at 600 vac; provides overload and short circuit protection; adjustable magnetic trip: low: 1125a, high: 2250a; terminal type: i-line connection (on end), 3 and lugs (off end), 3; wire size: no. 3/0 to 350 awg/kcmil

NSN
National Stock Number:
5925-01-587-5767 5925015875767
TXT
Description:
Circuit Breaker
INC
INC
Item Name Code:
00136
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Multipole-single actuator type
MRC:
A measurement of the longest dimension of the body,in distinction from width.ADAQ
Body Length:
4.500 inches
MRC:
The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.ADTV
Case Material:
Plastic
MRC:
The national stock number or the identification information of the end equipment for which the item is a part.AGAV
End Application:
For use with i-line panelboards and switchboards
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
3
MRC:
Indicates the type and number of facilities by which the item is mounted.AXHR
Mounting Facility Type And Quantity:
I-line plug-on
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
225.0 amperes ac all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
600.0 ac all locations
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent all locations
MRC:
The means provided to reposition the mechanism so that the device is ready to function.CPRQ
Reset Method:
Manual
MRC:
Indicates the type and number of actuators provided for manual control.CPRT
Manual Actuator Type And Quantity:
1 toggle
MRC:
Denotes the action imparted by actuator operation.CPRW
Actuator Function:
Trip-reset
MRC:
An indication of the designated position of the actuator.CPRX
Actuator Position Designation:
At pole two
MRC:
Indicates the arrangement of the externally connected actuators.CPRY
External Actuator Linkage Arrangement:
One, two, and three linked

Similar Circuit Breakers

« Circuit Breakers Catalog
Compare Now »
Clear | Hide